Nelson :: Application
 
 
 
To view the Application/System Index, you may browse through the page with the scroll bar or select a link below to jump to the section of your choice.
   
 
Concrete Floors Control Cable
  Penetrating Item
(Size and Type)
Sleeve
O - Opt
R - Req'd
Point Contact Assembly Thickness F Rating Nelson Product UL System FS Detail
  2C #10 AWG     X   4 1/2   2   ES1399/LBS3   C-AJ-8162  FS0641r1
  7C #24 AWG     X   4 1/2   2   ES1399/LBS3   C-AJ-8162  FS0641r1
  3C #18 AWG or 1C #3 AWG  R       8   3   CLK   C-BJ-3014  FS0192r5
  15% fill, #2-14 AWG         4½   3   FSP   C-AJ-3003  FS0002r3
  4C #2 AWG armored, METAL CLAD, 6" hollow-core         4½   2   FSP   C-AJ-3090  FS0127r4
  7C #12 AWG         3¼   2   MPS   C-AJ-3047  FS0087r4
  7C #12 AWG  R       4½   2   PLW   C-AJ-3093  FS0130r4
  7C #12 AWG         4½   2, 3   MCT   C-AJ-3048  FS0114r4
  25% fill, 7C #12 AWG         4½   2   ES1399   C-AJ-3235  FS0518r1
  16C #16 AWG, also 6" hollow-core  O       4½   2   LBS3   C-AJ-3225  FS0532r1
  4C #12 AWG  O       4½   2   LBS3   C-AJ-3225  FS0532r1
  7C #16 AWG  O       2½   2   LBS3   C-AJ-3224  FS0533r1
  7C #16 AWG  O       4½   3   LBS3   C-AJ-3227  FS0535r1
   
Non Toxic, Non Hazardous
Not Harmful to Plants or Animals,
[ No PBDes - Polybrominated Diphenyl ethers]