Nelson :: Application
 
 
 
To view the Application/System Index, you may browse through the page with the scroll bar or select a link below to jump to the section of your choice.
   
 
Concrete Floors Communications Cable
  Penetrating Item
(Size and Type)
Sleeve
O - Opt
R - Req'd
Point Contact Assembly Thickness F Rating Nelson Product UL System FS Detail
  15% fill, 25 pr. #24 AWG         4½   3   FSP   C-AJ-3003  FS0002r3
  15% fill, 25 pr. #24 AWG  R       4½   2   PLW   C-AJ-3093  FS0130r4
  30% fill, 25 pr. #24 AWG  R       4½   2   CLK   C-AJ-3094  FS0131r3
  100 pr. 72 Fiber optic         4½   2   MCT   C-AJ-3048  FS0114r4
  100 pr. #24 AWG         3¼   2   MPS   C-AJ-3047  FS0087r4
  70% fill, 100 pr. #24 AWG  O       4½   2   PCS/FSP   C-AJ-3118  FS0196r4
  13% fill, 100 pr. #24 telephone         4½   3   FSP   C-AJ-3004  FS0014r4
  36% fill, 240 pr. #24 AWG         8   2   CPS/FSP   C-BJ-4016  FS0094r3
  72 Fiber optic  R       4½   2   FSP   C-AJ-3089  FS0126r5
  4 pr. #18 AWG, multiple     X   2 1/2   1   WRS3/LBS3   F-A-8026  FS0660r0
  400 pr. #24 AWG comm. Cable bundles w/more         2½   2   ES1399   C-AJ-8118  FS0377r1
  25% fill, 100 pr. #24 AWG         4½   2   ES1399   C-AJ-3235  FS0518r1
  25 pr. #24 AWG         4½   2   LBS3   C-AJ-8141  FS0544r1
  100 pr. #24 AWG, also 6" hollow-core  O       4½   2   LBS3   C-AJ-3225  FS0532r1
  400 pr. #24 AWG telecomm.  O       2½   2   LBS3   C-AJ-3224  FS0533r1
  400 pr. #24 AWG telecomm.  O       4½   3   LBS3   C-AJ-3227  FS0535r1
  72 Fiber Optic  O       2½   2   LBS3   C-AJ-3224  FS0533r1
  72 Fiber optic         4½   2   LBS3   C-AJ-8141  FS0544r1
  72 Fiber Optic  O       4½   3   LBS3   C-AJ-3227  FS0535r1
   
Non Toxic, Non Hazardous
Not Harmful to Plants or Animals,
[ No PBDes - Polybrominated Diphenyl ethers]